1. Remove all plugs from the jacks in the protector
.
2. Remove (2) front screws marked “T
ray Release”.
3. Slide tray out from back of the protector
.
4. Remove punchdown wires on effected module (s).
5. Remove (2) screws on module.
6. Remove module and insert new module.
7. Attach (2) screws and punchdown wires in proper location.
8. Slide tray into chassis and fasten with (2) screws.
9. Insert plugs into proper jack locations.
CAUTION:
1. Never install telephone wiring during a lightning storm.
2.
Disconnect telephone lines before installing protector
.
3. Protector and equipment ground should be connected to a single common ground.
4. Make sure no electrical surges are on the lines when installing or removing circuit cards.
5. The protector shall be installed in accordance with the applicable requirements of the
National Electric Code, ANSI/NFP
A-70, Article 800, Section C.
Thank you for choosing ITW Linx DataLinx® 1200. The
DataLinx 1200 will provide the finest surge protection
available for Power Over Ethernet (POE), Voice Over
Internet Protocol (VOIP) and LAN needs.
INSTALLING DATALINX 1200 SERIES UNITS
Using four standard rack mounting screws (included)
mount DataLinx 1200 to a standard 19" rack cabinet.
Detach the two front panel screws. Pull the back of the
housing out to expose the 110 connectors. Carefully
punch-down input pairs, maintaining proper wire twist.
Wires must be 24 AWG and be punched-down in
c
ompliance with either TIA 568-A or 568-B standards.
See diagram below.
WIRING CONVENTIONS/DIAGRAM
DL1200 / DL1200-235
DL1200-POE
Position cable(s) into the cable exit slots on the back of
the housing. Position and secure a cable tie on each
cable to provide strain relief next to cable exit slots in the
protector housing.
Push the housing back in and secure the two front panel
screws.
IMPORTANT: Attach a #6 AWG wire to the Screw
Ground Lug (SGL-1) on back of the unit to a properly
grounded Ground Bus Bar
.
To ensure Cat 5e performance, connect a Cat 5e or better
patch cord to the DataLinx protector and the equipment
to be protected. In the extremely unlikely event that
everything does not work perfectly, stop and read the
t
roubleshooting section. If you continue to have prob-
lems, call ITW Linx Customer Service Department at
.
DATALINX 1200 FEATURES
—Solid-state, Primary and
Isolated Loop protection, UL 497 and 497B, Cat 5e per
TIA 568-A and TIA 568-B)
S
ingle Height Chassis (1U)
Replaceable 4-port Modules
—In the event of a cata-
strophic surge you will not need to replace the entire
unit, just the modules that have been effected.
TROUBLESHOOTING
1. Intermittent or no LAN connections.
Wires are not completely punched-down or are not
punched-down correctly. Visually inspect for any lose or
n
on-connected wires. Verify that wires are punched-
down in compliance with either TIA 568-A or 568-B
standards.
N
OTE:
I
f system operating voltage exceeds the listed
initial clamping voltage for your unit or if a surge is
present on the network, the port will be connected to
GND by design. Remove surge source or check the
system voltage.
If you continue to have trouble with your DataLinx 1200
or this section has not fixed the problem, please call
ITW Linx Customer Service at:
CAUTION:
1. Never install telephone wiring during a lightning storm.
2. Disconnect telephone lines before installing protector.
3
. Protector and equipment ground should be connected to
a single common ground.
4
. Make sure no electrical surges are on the lines when installing
or removing circuit cards.
5. The protector shall be installed in accordance with the
a
pplicable requirements of the National Electric Code,
ANSI/NFPA-70, Article 800, Section C.
Note:
1
. Many old buildings are inadequately wired. It is very common
for a building to be improperly grounded. Building wiring and
g
rounding must conform to applicable NEC (USA) or CEC
(Canada). Ground impedance is recommended to be 1 ohm or
less. Protectors will not function properly when connected
improperly or to a faulty ground.
2. The DataLinx 1200 and the connected equipment must be
indoors and in the same building.
9026-040-00 Rev
. 3
DATALINX INSTALLATION INSTRUCTIONS
Models: DL1200, DL1200-POE, DL1200-75, DL1200-235
DATALINX REPLACEMENT CARD INSTALLATION INSTRUCTIONS
DL1200-RC-16, DL1200-RC-POE, DL1200-RC-75 and DL1200-RC-235
12 GND11109
LINE
87 6 5 43 21
DataLinx 1200
12 3456 78910 1112
TRAY RELEASE TRAY RELEASE
LINE
800-336-LINX • itwlinx.com
© ITW Linx 2006. ITW and the Linx logo are registered US trademarks of Illinois T
ool W
orks Inc.
FRONT PANEL—DataLinx 1200
12 GND11109
L
INE
87 6 5 43 21
DataLinx 1200
1
2 3456 78910 1112
T
RAY RELEASE TRAY RELEASE
L
INE
REAR PANEL—DataLinx 1200
W-O
W-G
W-BL
G
T568A
O
T568B
G
O
BL
W-G
BL
W-O
W-BL
BR
W-BR
78364521
W-BR
BR
W-O
W-G
W-BL
G
T568A
O
T568B
G
O
BL
W-G
BL
W-O
W-BL
BR
W-BR
78364521
W-BR
BR
P
ins 4, 5, 7 and 8 clamp at 62V,
Pins 1, 2, 3 and 6 clamp at 16V.
D
L1200—All pins clamp at 16V.
D
L1200-235—All pins clamp
a
t 235V
.
DL1200-75—All pins clamp
at 75V.